Open battery ageing data · TEMPEST 280 Ah LFP
TEMPEST ageing data: a 280 Ah LFP cell over 700 cycles at 1C
The TEMPEST cell dataset (Gray and Vagg, University of Bath, for the EU project TEMPEST, 2026) tested a 280 Ah prismatic LFP cell that the record calls the “LIC” cell. The record does not name its maker or its model. It holds two test series: five capacity tests at 15 to 35 °C, and an ageing test of 700 cycles at 1C (280 A) in blocks of 50. Before the first block and after each, a reference test measured the capacity at 0.1C and took 10 s pulses at 50 % state of charge. The record does not say whether one physical cell ran both series. Lemonergy computed one row per cycle or test from the published files. Only the reference tests are drawn: the 1C cycles are logged every 10 s, too coarse to read capacity fade from.
Download every row (CSV, 129 kB)Manifest (JSON): files, hashes, unitsChart and Excel downloadOriginal dataset
Free to download, no account needed. Or read it straight into Python:
import pandas as pd
cycles = pd.read_csv("https://lemonergy.com/data/ageing/tempest-lic-280ah-2026/cycles.csv")- Cells
- 1 cell type in 2 test series, prismatic (the record: '280 Ah prismatic LFP cell'); maker not stated
- Chemistry
- LFP (as the record names the cell)
- Nominal capacity
- 280 Ah
- Rows
- 720, one row each
- Test programmes
- 2
- Published by
- University of Bath, for the EU project TEMPEST
- Licence
- CC BY 4.0
- Files retrieved
- 2026-11-14
Source: 280 Ah prismatic LFP cell: characterisation and aging data (TEMPEST 'LIC' cell; capacity tests, 1C ageing cycles and reference tests), University of Bath, for the EU project TEMPEST, doi:10.5281/zenodo.20813753. Licence: CC BY 4.0.
Cite: Gray, R., Vagg, C. 280 Ah prismatic LFP cell: characterisation and aging data. Zenodo (2026). doi:10.5281/zenodo.20813753
Licence and how to cite · Data quality · Every source file, by SHA-256
Capacity fade, reference test by reference test
Discharge capacity of each 0.1C reference test, against the 1C cycles run before it. The 1C ageing cycles and the five capacity tests at 15 to 35 °C are in the CSV, not drawn. Point at a chart to read the values; download them as Excel.
The chart needs JavaScript; every cell’s values are in the table below and in the CSV.
Point at or touch a chart to read every cell’s value at that cycle. Drag across it with a mouse to zoom in. Click a line, or a cell’s name in the legend or table, to show that cell on its own; the others turn grey.Touch a chart to read the values at a cycle. Tap a cell’s name in the legend or the table to show it on its own; the others turn grey.
| Cell | Rows (cycles and tests) | Points drawn | First (Ah) | Last (Ah) | Last / first |
|---|
Every cell
First and last discharge capacity of the rows the chart draws, for both test series. Every row of every cell, with all its values, is in the CSV (129 kB).
| Programme | Cell | Rows (cycles and tests) | Points drawn | First (Ah) | Last (Ah) | Last / first |
|---|---|---|---|---|---|---|
| ageing | LIC-ageing | 715 | 15 | 301.578 | 280.259 | 92.9 % |
| characterisation | LIC-characterisation | 5 | not drawn | – | – | – |
Test programmes
- ageing. 700 cycles at 1C (280 A CC-CV to 3.65 V, 280 A CC to 2.5 V) in 14 blocks of 50, and 15 reference tests (before the first block and after each). Drawn: 0.1C (28 A) reference capacity tests, before the first block of 50 cycles and after each.
- characterisation. 5 capacity tests, one per file XXC_capacity.csv (15, 20, 25, 30, 35 °C). Not drawn: capacity tests of the new cell type at five temperatures (15 to 35 °C), not ageing; there is no ageing axis to draw them against; its cycles are in the CSV.
Columns of the CSV
Read with battery-data tools/convert_tempest_lic.py from the two zips, without unpacking. A step is a run of samples of one kind: charge (current above +0.5 A), discharge (below -0.5 A) or rest. Charge and discharge are integrated per step as each sample's current over the interval since the sample before it, the step's first sample included (the tools/cyclers.py rule right_rectangle_boundary, applied per step); this rule reproduces 19 of the 20 capacities the publishers list to 5e-06 Ah or better (the other is under gates.differ and in the caveats). A row is a charge step followed by the next discharge step of the same kind: a 1C charge with a 1C discharge (ageing cycle), or a full 0.1C charge to 3.65 V with a 0.1C discharge to 2.5 V (capacity test). The six 10 s pulses before each capacity test of the ageing file belong to its reference-test row. Other steps are counted, not made into rows (unpaired_steps under source_files). Values rounded: Ah to 5 decimals, volts and efficiency to 4 and 5, mOhm to 4, degC to 2.
| Column | Unit | Meaning |
|---|---|---|
batch | – | 'characterisation' (the five capacity tests at 15-35 °C, capacity_hppc_entropy.zip) or 'ageing' (aging.zip) |
cell | – | the test series: 'LIC-characterisation' or 'LIC-ageing'. The record does not say whether both used the same physical cell |
cycle | – | row number within the cell, 1-based, in time order (characterisation: one per temperature, 15 to 35 °C) |
label | – | what the row is (capacity test at a temperature, ageing cycle at 1C, or the capacity test of a reference test), with each step's C-rate (of 280 Ah), current, CC or CC-CV and end voltage as the data show |
cycles_1c_before | – | ageing rows: 1C cycles completed before this row; for a reference test this is the publishers' Total_cycles (0, 50, ... 700) |
temperature_c | degC | characterisation rows: the test temperature, as the file name and readme state ('XXC_capacity ... where XX is the temperature in degC'); blank for ageing rows, whose test temperature the record does not state |
charge_ah | Ah | charge step integrated from current: each sample's current over the interval since the sample before it, the step's first sample included |
discharge_ah | Ah | discharge step integrated the same way |
discharge_ah_reported | Ah | the publishers' capacity for this test: LIC_capacity_analysis.csv (characterisation) or LIC_aging_analysed.csv Capacity_Ah (reference tests); blank for 1C ageing cycles |
coulombic_efficiency | – | discharge_ah / charge_ah |
v_max | V | highest voltage in the charge and discharge steps |
v_min | V | lowest voltage in the charge and discharge steps |
duration_s | s | from the first sample of the charge step to the last sample of the discharge step |
start_test_time_s | s | first sample of the charge step, on the file's own clock (each characterisation file starts its own) |
surface_temp_min_c | degC | lowest cell-surface temperature during the charge and discharge steps: the middle of the largest face (ageing: midT; characterisation: Temperature_K converted) |
surface_temp_max_c | degC | highest cell-surface temperature during the charge and discharge steps, same sensor |
edge_temp_max_c | degC | ageing rows: highest temperature at the edge sensor (largest face, 10 % of the distance from the top; edgeT); blank for characterisation rows, whose files have one sensor |
dcir_dis_02c_10s_mohm | mOhm | reference tests: 10 s discharge pulse at 0.2C (56 A) at 50 % SoC: |voltage at the pulse's last sample - voltage of the last rest sample before it| / mean pulse current; computed by Lemonergy |
dcir_cha_02c_10s_mohm | mOhm | reference tests: 10 s charge pulse at 0.2C (56 A) at 50 % SoC: |voltage at the pulse's last sample - voltage of the last rest sample before it| / mean pulse current; computed by Lemonergy |
dcir_dis_05c_10s_mohm | mOhm | reference tests: 10 s discharge pulse at 0.5C (140 A) at 50 % SoC: |voltage at the pulse's last sample - voltage of the last rest sample before it| / mean pulse current; computed by Lemonergy |
dcir_cha_05c_10s_mohm | mOhm | reference tests: 10 s charge pulse at 0.5C (140 A) at 50 % SoC: |voltage at the pulse's last sample - voltage of the last rest sample before it| / mean pulse current; computed by Lemonergy |
dcir_dis_1c_10s_mohm | mOhm | reference tests: 10 s discharge pulse at 1.0C (280 A) at 50 % SoC: |voltage at the pulse's last sample - voltage of the last rest sample before it| / mean pulse current; computed by Lemonergy |
dcir_cha_1c_10s_mohm | mOhm | reference tests: 10 s charge pulse at 1.0C (280 A) at 50 % SoC: |voltage at the pulse's last sample - voltage of the last rest sample before it| / mean pulse current; computed by Lemonergy |
ohmic_resistance_mohm_reported | mOhm | reference tests: the publishers' Ohmic_res_Ohm (LIC_aging_analysed.csv, 'calculated from reference pulse test between blocks (1C discharge pulse)'), in mOhm; the record does not say at what time after the pulse start it is read |
Data quality
No per-cell quality verdict was recorded for this dataset. Read the caveats below before comparing cells.
Before comparing cells
- Maker and model are not stated anywhere in the record or its files; the cell is filed under the library's placeholder maker as 'TEMPEST LIC 280Ah'. Do not compare it with a named 280 Ah LFP cell as if it were one.
- Whether the characterisation and the ageing used the same physical cell is not stated; `cell` names the test series. The ageing file's first capacity test (301.58 Ah) and the 25 °C characterisation test (302.31 Ah) are close but not equal.
- The 1C ageing cycles are logged every 10 s, so one sample is 0.78 Ah at 280 A: their charge_ah and discharge_ah move in steps of about 0.78 Ah, and the step's first and last 10 s are counted at the sampled current. Compare capacity fade on the reference-test rows (0.1C, logged every 1 s), not on the 1C rows.
- The 1C discharges' v_min is the last logged voltage (2.53-2.59 V), above the 2.5 V cut-off reached between samples.
- Reference tests: the capacity is the 0.1C discharge to 2.5 V after a 0.1C CC-CV charge to 3.65 V. The pulses come before it, at 50 % SoC set by a 0.1C charge of 150.8 Ah (by time) from the discharged cell and a day's rest; the pulse resistances are this file's own, computed by Lemonergy with the method under columns; the publishers' ohmic resistance is beside them (it lies between the resistance at 20 ms and at 30 ms into the 1C discharge pulse of the first test, 0.294 and 0.303 mOhm against 0.299 mOhm; the record does not say how it was read).
- One reference capacity differs from the publishers' list, after 250 cycles: The publishers list 291.7386513 Ah for the reference test after 250 cycles; the log's capacity test there (0.1C CC-CV charge, then 0.1C discharge to 2.5 V, both whole, 1 s samples) gives 287.30529 Ah, below the 287.88 Ah of the test after 300 cycles. Just before this reference test the log joins two recordings (voltage 2.820 V to 3.329 V and surface temperature 31.7 to 34.9 °C between two rest samples 1 s apart, at t = 3477335 s) and a 0.1C discharge of 280.0 Ah stops by time at 2.74 V. The record does not explain the difference; both values are kept. Use discharge_ah_reported for the publishers' figure.
- The ageing log holds 2 voltage jumps of more than 0.15 V between two rest samples with no current (rest_voltage_jumps under source_files): the cell's voltage and temperature change at once, as if two recordings were joined with a charge between them unlogged. The steps after them that pair with nothing are counted under unpaired_steps; no row spans a jump.
- Not imported: the HPPC time series (the publishers' R0 per temperature and SoC is under characterisation), the pulses' and partial steps' time series, and the 24 h rests. The earlier record Zenodo 19632939 holds the same characterisation files (same md5) and is superseded by this one.
- Two further TEMPEST LIC records exist on Zenodo (15228104 and 15773220, 'TEMPEST LIC cell capacity data 1': capacity tests at C/2, C/5 and C/10 at 5-35 °C, 2024); they are not part of this record and not imported here.
- The maker and model of this cell are not stated anywhere in the record. Each point is a reference test: the 0.1C capacity, against the 1C cycles run before it. Integrated from the log's current, 19 of the 20 capacities the publishers list come out the same to 0.0001 Ah. The one that differs is after 250 cycles: the publishers list 291.74 Ah where the log gives 287.31 Ah, less than the 287.88 Ah of the test after 300 cycles. The record does not explain the difference. The chart draws the log's value; both are kept in the CSV (discharge_ah and discharge_ah_reported). The five capacity tests at 15 to 35 °C are in the CSV, not drawn.
Licence and how to cite
The values are published under CC BY 4.0, as the source is. Credit it as follows.
Cite: Gray, R., Vagg, C. 280 Ah prismatic LFP cell: characterisation and aging data. Zenodo (2026). doi:10.5281/zenodo.20813753
Credit: Data: Gray, R., Vagg, C. (University of Bath), EU project TEMPEST (Horizon Europe grant 101103681; UKRI 10075481), doi:10.5281/zenodo.20813753, CC BY 4.0. Per-cycle values computed by Lemonergy (battery-data).
Values pinned to battery-data revision e85dd43. The manifest names every source file by its SHA-256; the CSV’s own SHA-256 is ba25d6bdcb1f0e04d5c5d021304555125057e8a569331dde66eeeaf24fe80ca4.
Related
- XJTU battery ageing data: 55 Lishen 18650 cells, cycle by cycle
- CALCE CS2 battery ageing data: 15 LiCoO2 cells, cycle by cycle
- Tongji/KIT NCA ageing data: 66 18650 cells, cycle by cycle
- Tongji/KIT NCM ageing data: 55 18650 cells, cycle by cycle
- Tongji/KIT NCM+NCA ageing data: 9 18650 cells at three discharge rates
- Michigan VTC6 data: 194 characterisations of 70 aged 18650 cells
- CMU eVTOL battery data: 22 VTC6 cells under aircraft missions
- NASA PCoE battery ageing data: 34 18650 cells, cycle by cycle
- Oxford battery degradation data: 8 Kokam pouch cells, test by test
- UConn LFP ageing data: 64 18650 cells under 11 cycling conditions
- HYDRA ageing data: 32 LG MJ1 18650 cells under ship-like cycling
- REBELION ageing data: 160 Samsung 50E cells, four cycling strategies
- LiBforSecUse ageing data: 34 18650 NMC811 cells, 13 life-cycle tests
- VERSAPRINT cycle data: one Lishen 51 Ah cell, nine cycles
- EVERLASTING ageing data: 28 Samsung 35E cells under drive cycles
- FreeTwinEV module data: four Molicel P45B cells in parallel, 14 runs
- All open battery ageing data on Lemonergy