Battery knowledge · High-voltage and functional safety
Arcing
Current continuing through ionised gas across a gap, typically between contacts as they separate. An AC arc goes out by itself at each current zero, a hundred times a second at 50 Hz; a DC arc has no zero and keeps burning until it is stretched and cooled so far that its voltage exceeds the source’s, which makes high-voltage DC far harder to interrupt.
- Also called
- electric arc, DC arc
Example
High-voltage and functional safety: an example situation
Normal-operation current limits do not demonstrate correct contactor behavior under a welded-contact or sensor fault.
Read Arcing alongside Arc flash in this context. The burst of heat, light and pressure released by a fault arc. The hazard to a worker is rated as incident energy at working distance; 1.2 cal/cm² is the usual onset of second-degree burns. Large battery systems can feed fault currents of many kiloamperes, so arc flash sets protective clothing and approach limits under NFPA 70E.
Use in Lemonergy
Relate protection to faults, detection and response.
This is a reference concept. No executable Lemonergy block has been verified for this term.