Reactive power support

Supplying or absorbing reactive power to hold local grid voltage within limits. A battery’s inverter can do it at any state of charge, since reactive power circulates rather than draining stored energy, but it shares the inverter’s apparent-power rating with real power: a 1 MVA inverter exporting 0.8 MW has 0.6 Mvar left.

Also called
reactive power, volt-var control, var support
Unit
var
Relationship
S² = P² + Q²

Example

Read an apparent-power limit

For an ideal converter limited to 10 kVA and operating at 8 kW active power, the circular capability relation allows up to 6 kvar magnitude. Real equipment capability can impose tighter limits.

Explore the graph

The apparent-power circle bounds combinations of active and reactive power.

Ideal apparent-power envelope
Ideal apparent-power envelopeActive power P (MW) versus Reactive power Q (Mvar). Positive Q bound; Negative Q bound. Interpretation follows the graphs.-1-1-0.5-0.5000.50.511Active power P (MW)Reactive power Q (Mvar)
Positive Q boundNegative Q bound (dashed)

At P = 0.8 MW, the ideal rating permits up to ±0.6 Mvar.

S² = P² + Q²; |Q| ≤ √(S² − P²)

Illustrative model. Ideal fixed apparent-power limit. Actual converter capability also depends on current, voltage, temperature, DC-link and control limits.

Use in Lemonergy

Start with mission energy, peak power and operating conditions.

This is a reference concept. No executable Lemonergy block has been verified for this term.

References & further reading

Further reading on this topic

These sources provide broader context; they are not presented as citations for every statement in this entry.

  1. DOE/EPRI 2013 Electricity Storage Handbook in Collaboration with NRECA

    Sandia National Laboratories · 2013

    Topic background · Storage technologies and grid services. The publisher notes that its historical cost and deployment figures are outdated.