Coolant pressure and temperature boundary
Fixes pressure and inflowing coolant temperature at one liquid terminal. In the plate example, inlet and outlet are two instances of this same boundary.
- Implementation ID
liquid-reservoir- Reviewed
- 2026-10-27
Behavior
This ideal boundary supplies or receives coolant while holding its configured pressure and inflow temperature. A pressure difference across the cooling plate determines the flow. When flow reverses, the receiving boundary becomes the supplying boundary. Outgoing coolant carries the plate outlet temperature; the receiving boundary does not clamp that outlet temperature.
Interface
What inlet and outlet actually mean
Both are coolant boundary blocks. Their names describe the example role; their pressures determine the actual direction.
Scroll the diagram sideways to see every connection.
The same boundary type can supply or receive coolant. Its temperature is the inflow condition; it does not clamp the exiting coolant temperature.
| Name | Direction | Unit | Meaning |
|---|---|---|---|
a | terminal | Pa / kg/s / K / W | Thermal-liquid terminal connecting this boundary to a cooling plate. The boundary fixes pressure and the temperature used when coolant flows out of the boundary. Mass and enthalpy reaction flows balance the connected plate. |
pressure | output | Pa | The configured absolute pressure at this boundary. |
temperature | output | K | The configured inflow temperature, not a measurement of returning coolant. |
massFlow | output | kg/s | Net mass flow into this boundary. Negative when it supplies the plate; positive when it receives returning coolant. |
enthalpyFlow | output | W | Net advected enthalpy flow into this boundary. Returning coolant uses its plate outlet temperature. |
Parameters
Defaults are initial model values. Select values for your own model and operating conditions.
| Parameter | Unit | Default | Meaning and limits |
|---|---|---|---|
Boundary pressurepressurePa | Pa | 101325 | Absolute pressure held at this liquid node. Set a pressure difference between the two boundaries to drive coolant flow. Minimum 1; Maximum 1000000000.0 |
Coolant supply temperaturetemperatureK | K | 300 | Temperature of coolant supplied by this boundary. It is used as the inlet condition only when flow leaves this boundary. Minimum 0; Maximum 5000 |
Equations and rules
pressure = pressurePainflow temperature = temperatureKboundary massFlow + mass flow leaving the boundary = 0
Worked example
Two boundaries in the U-channel plate example
The existing U-channel example sets inlet to 200000 Pa and outlet to 100000 Pa, both at 300 K. The plate carries 0.1 kg/s from inlet to outlet. These checks describe the boundary within the released plate network, not a separate standalone validation.
Open Studio example →| Output | Time (s) | Expected value | Unit | Absolute tolerance |
|---|---|---|---|---|
Supply boundary pressureinlet/pressure | 0 | 200000 | Pa | 1e-06 |
Supply coolant temperatureinlet/temperature | 0 | 300 | K | 1e-06 |
Mass supplied by inlet boundaryinlet/massFlow | 0 | -0.1 | kg/s | 1e-09 |
Use in a workflow
Edge-cooled plate worked example
A plate with four thermal contacts and a defined coolant path. Explore which body connects to each contact and how pressure drives coolant through the plate.
- Coolant inlet boundary: Sets 200 kPa and 300 K at plate a; supplies coolant for the positive pressure difference.
- Coolant outlet boundary: Sets 100 kPa at plate b; receives coolant. Its 300 K supply temperature is used if flow reverses.
Parallel-channel plate worked example
A plate with four thermal contacts and a defined coolant path. Explore which body connects to each contact and how pressure drives coolant through the plate.
- Coolant inlet boundary: Sets 200 kPa and 300 K at plate a; supplies coolant for the positive pressure difference.
- Coolant outlet boundary: Sets 100 kPa at plate b; receives coolant. Its 300 K supply temperature is used if flow reverses.
U-channel plate worked example
A plate with four thermal contacts and a defined coolant path. Explore which body connects to each contact and how pressure drives coolant through the plate.
- Coolant inlet boundary: Sets 200 kPa and 300 K at plate a; supplies coolant for the positive pressure difference.
- Coolant outlet boundary: Sets 100 kPa at plate b; receives coolant. Its 300 K supply temperature is used if flow reverses.
Connected concepts
Limits and interpretation
- Ideal fixed pressure and inflow temperature, not a finite tank, pump or radiator model. Each coolant node requires exactly one explicit boundary in the current bounded plate solver.
- Boundary checks reuse the existing released U-channel network; they are synthetic model checks, not measured equipment data.
Scientific and mathematical references
These sources explain the scientific and mathematical background. The behavior, interface and limits above define the Lemonergy implementation; a citation does not imply every model option in the source is implemented.
- University Physics Volume 2, §1.6: Mechanisms of Heat Transfer
OpenStax, Rice University
Technical reference · Conduction, convection, radiation and thermal resistance.
Implementation sources
This reference follows the public interface and numerical checks for the verified Studio release. Synthetic examples and model limits remain as documented above.
Contract: Lemonergy Studio public contract · Verification record: verification-2026-10-27
Production revision: e76cadfc203e15eb41f3478d8b1044a5b851953d · Verified: 2026-10-28
docs/glossary/native-block-verification.json
This implementation and its workflow uses (JSON) · Knowledge graph (JSON-LD)