  "node": {
    "id": "term:fuse-coordination",
    "type": "Term",
    "label": "Fuse coordination",
    "properties": {
      "id": "fuse-coordination",
      "name": "Fuse coordination",
      "aka": [
        "selectivity",
        "discrimination",
        "protection coordination"
      ],
      "section": "topic-hvsafety",
      "definition": "Choosing the ratings of fuses and breakers in series so that a fault opens only the device nearest to it and the remainder of the system keeps running. For fuses, the downstream fuse’s total clearing I²t must stay below the upstream fuse’s pre-arcing I²t; in a pack, a cell or module fuse should act before the main fuse or pyrofuse.",
      "formula": "I²t_clearing(downstream) < I²t_pre-arcing(upstream)",
      "related": [
        "fuse",
        "pyrofuse",
        "battery-disconnect-unit",
        "external-short-circuit",
        "series-parallel"
      ],
      "example": {
        "title": "Compare clearing and pre-arcing energy",
        "text": "If a downstream fuse has 500 A²s clearing I²t and the upstream fuse has 1000 A²s pre-arcing I²t under the specified fault conditions, the inequality is satisfied. The full time-current curves and manufacturer coordination rules are still required."
      },
      "url": "https://lemonergy.com/learn/glossary/fuse-coordination/",
      "mentions": []
    }
  },
  "edges": [
    {
      "id": "edge:5094",
      "source": "term:fuse-coordination",
      "target": "topic:topic-hvsafety",
      "type": "belongsTo",
      "properties": {
        "sourceFile": "terms.json"
      }
    },
    {
      "id": "edge:5095",
      "source": "term:fuse-coordination",
      "target": "term:fuse",
      "type": "relatedTo",
      "properties": {
        "sourceFile": "terms.json",
        "meaning": "Related context; not a causal claim"
      }
    },
    {
      "id": "edge:5096",
      "source": "term:fuse-coordination",
      "target": "term:pyrofuse",
      "type": "relatedTo",
      "properties": {
        "sourceFile": "terms.json",
        "meaning": "Related context; not a causal claim"
      }
    },
    {
      "id": "edge:5097",
      "source": "term:fuse-coordination",
      "target": "term:battery-disconnect-unit",
      "type": "relatedTo",
      "properties": {
        "sourceFile": "terms.json",
        "meaning": "Related context; not a causal claim"
      }
    },
    {
      "id": "edge:5098",
      "source": "term:fuse-coordination",
      "target": "term:external-short-circuit",
      "type": "relatedTo",
      "properties": {
        "sourceFile": "terms.json",
        "meaning": "Related context; not a causal claim"
      }
    },
    {
      "id": "edge:5099",
      "source": "term:fuse-coordination",
      "target": "term:series-parallel",
      "type": "relatedTo",
      "properties": {
        "sourceFile": "terms.json",
        "meaning": "Related context; not a causal claim"
      }
    },
    {
      "id": "edge:5100",
      "source": "term:fuse-coordination",
      "target": "visual:fuse-integral",
      "type": "illustratedBy",
      "properties": {
        "sourceFile": "visual-pages.json"
      }
    }
  ],
  "neighbors": [
    {
      "id": "topic:topic-hvsafety",
      "type": "Topic",
      "label": "High-voltage and functional safety",
      "properties": {
        "id": "topic-hvsafety",
        "name": "High-voltage and functional safety",
        "lede": "Keeping people safe from the pack’s voltage and keeping its electronics safe when they fail: insulation, switching, fusing and the functional-safety process.",
        "context": "Relate protection to faults, detection and response.",
        "example": "Normal-operation current limits do not demonstrate correct contactor behavior under a welded-contact or sensor fault.",
        "lesson_url": "https://lemonergy.com/learn/fundamentals/battery-basics/",
        "lesson_label": "Open battery basics"
      }
    },
    {
      "id": "term:fuse",
      "type": "Term",
      "label": "Fuse",
      "properties": {
        "id": "fuse",
        "name": "Fuse",
        "section": "topic-hvsafety",
        "definition": "A link that melts and opens the circuit when current exceeds its rating. Packs use a main fuse in the high-voltage path and often a small fuse on each parallel cell connection, so one shorted cell does not drain its neighbours into the fault.",
        "related": [
          "external-short-circuit",
          "pyrofuse",
          "battery-disconnect-unit",
          "series-parallel",
          "cell-level-fuse"
        ],
        "url": "https://lemonergy.com/learn/glossary/fuse/",
        "mentions": []
      }
    },
    {
      "id": "term:pyrofuse",
      "type": "Term",
      "label": "Pyrofuse",
      "properties": {
        "id": "pyrofuse",
        "name": "Pyrofuse",
        "aka": [
          "pyrotechnic disconnect"
        ],
        "section": "topic-hvsafety",
        "definition": "A high-voltage disconnect fired by a small pyrotechnic charge on command, typically from the airbag controller in a crash. It cuts the pack from the vehicle in milliseconds, faster and more reliably than a contactor can open under fault current.",
        "related": [
          "fuse",
          "contactor",
          "battery-disconnect-unit",
          "high-voltage-interlock"
        ],
        "url": "https://lemonergy.com/learn/glossary/pyrofuse/",
        "mentions": []
      }
    },
    {
      "id": "term:battery-disconnect-unit",
      "type": "Term",
      "label": "Battery disconnect unit",
      "properties": {
        "id": "battery-disconnect-unit",
        "name": "Battery disconnect unit",
        "abbr": "BDU",
        "aka": [
          "battery junction box"
        ],
        "section": "topic-hvsafety",
        "definition": "The box inside the pack that holds the contactors, pre-charge circuit, main fuse or pyrofuse and current sensor, where the pack’s high-voltage connections are made and broken.",
        "related": [
          "contactor",
          "pre-charge",
          "fuse",
          "pyrofuse",
          "current-sensor"
        ],
        "url": "https://lemonergy.com/learn/glossary/battery-disconnect-unit/",
        "mentions": []
      }
    },
    {
      "id": "term:external-short-circuit",
      "type": "Term",
      "label": "External short circuit",
      "properties": {
        "id": "external-short-circuit",
        "name": "External short circuit",
        "section": "topic-safety",
        "definition": "A low-resistance connection between the terminals outside the cell, driving currents of hundreds of amperes. Fuses, the current interrupt device and a positive-temperature-coefficient element are the layers of protection against it.",
        "related": [
          "internal-short-circuit",
          "fuse",
          "current-interrupt-device",
          "ptc",
          "short-circuit-test"
        ],
        "url": "https://lemonergy.com/learn/glossary/external-short-circuit/",
        "mentions": []
      }
    },
    {
      "id": "term:series-parallel",
      "type": "Term",
      "label": "Series and parallel connection",
      "properties": {
        "id": "series-parallel",
        "name": "Series and parallel connection",
        "aka": [
          "xSyP"
        ],
        "section": "topic-pack",
        "definition": "Cells in series add their voltages; cells in parallel add their capacities and share current. A pack is described as, for example, 96s4p: 96 groups in series, each of 4 cells in parallel. Series strings need balancing; parallel groups self-balance through their shared terminals.",
        "formula": "V = n_s·V_cell, Q = n_p·Q_cell",
        "related": [
          "module",
          "cell-balancing",
          "pack-voltage",
          "volt",
          "fuse"
        ],
        "lesson": "fundamentals/battery-basics/#cell-module-pack",
        "example": {
          "title": "Assemble an ideal 4s2p pack",
          "text": "Eight identical 3.6 V, 5 Ah cells arranged as four series groups with two cells in parallel give 14.4 V nominal, 10 Ah and 144 Wh. Interconnect losses, cell variation and usable voltage limits are additional constraints."
        },
        "url": "https://lemonergy.com/learn/glossary/series-parallel/",
        "mentions": []
      }
    },
    {
      "id": "visual:fuse-integral",
      "type": "Visual",
      "label": "Accumulated current stress is an integral",
      "properties": {
        "title": "Accumulated current stress is an integral",
        "summary": "Compare an illustrative fault integral with two hypothetical device limits.",
        "readout": "At 60 A, an integral of 1000 A²·s is reached in 0.2778 s.",
        "formula": "I²t = ∫ I(t)² dt",
        "note": "Both thresholds are invented teaching values. Constant fault current is assumed; no arc, current-limiting behavior or validated protection design is modeled.",
        "software": {
          "status": "reference",
          "label": "Reference concept",
          "body": "This explains I²t accounting. Actual fuse coordination needs manufacturer time-current curves, clearing and pre-arcing data, DC voltage and prospective fault-current conditions.",
          "href": "../chapter-1/"
        },
        "html": "<figure class=\"visual-figure\"><figcaption>Illustrative fault integral</figcaption><svg class=\"visual-chart\" viewBox=\"0 0 360 330\" role=\"img\" aria-labelledby=\"static-fuse-integral-0-title static-fuse-integral-0-desc\"><title id=\"static-fuse-integral-0-title\">Illustrative fault integral</title><desc id=\"static-fuse-integral-0-desc\">Fault duration (s) versus Accumulated I²t (A²·s). Constant-current integral; Example downstream clearing = 1000; Example upstream pre-arcing = 3000. Interpretation follows the graphs.</desc><path d=\"M74,238h268\" stroke=\"currentColor\" opacity=\".13\"/><text x=\"64\" y=\"242\" text-anchor=\"end\" font-size=\"13\" fill=\"currentColor\">0</text><text x=\"74\" y=\"265\" text-anchor=\"middle\" font-size=\"13\" fill=\"currentColor\">0</text><path d=\"M74,188.5h268\" stroke=\"currentColor\" opacity=\".13\"/><text x=\"64\" y=\"192.5\" text-anchor=\"end\" font-size=\"13\" fill=\"currentColor\">900</text><text x=\"141\" y=\"265\" text-anchor=\"middle\" font-size=\"13\" fill=\"currentColor\">0.25</text><path d=\"M74,139h268\" stroke=\"currentColor\" opacity=\".13\"/><text x=\"64\" y=\"143\" text-anchor=\"end\" font-size=\"13\" fill=\"currentColor\">1,800</text><text x=\"208\" y=\"265\" text-anchor=\"middle\" font-size=\"13\" fill=\"currentColor\">0.5</text><path d=\"M74,89.5h268\" stroke=\"currentColor\" opacity=\".13\"/><text x=\"64\" y=\"93.5\" text-anchor=\"end\" font-size=\"13\" fill=\"currentColor\">2,700</text><text x=\"275\" y=\"265\" text-anchor=\"middle\" font-size=\"13\" fill=\"currentColor\">0.75</text><path d=\"M74,40h268\" stroke=\"currentColor\" opacity=\".13\"/><text x=\"64\" y=\"44\" text-anchor=\"end\" font-size=\"13\" fill=\"currentColor\">3,600</text><text x=\"342\" y=\"265\" text-anchor=\"middle\" font-size=\"13\" fill=\"currentColor\">1</text><path d=\"M74,40v198h268\" fill=\"none\" stroke=\"currentColor\" opacity=\".3\"/><polyline fill=\"none\" stroke=\"#2459a8\" stroke-width=\"2.8\" points=\"74.00,238.00 76.68,236.02 79.36,234.04 82.04,232.06 84.72,230.08 87.40,228.10 90.08,226.12 92.76,224.14 95.44,222.16 98.12,220.18 100.80,218.20 103.48,216.22 106.16,214.24 108.84,212.26 111.52,210.28 114.20,208.30 116.88,206.32 119.56,204.34 122.24,202.36 124.92,200.38 127.60,198.40 130.28,196.42 132.96,194.44 135.64,192.46 138.32,190.48 141.00,188.50 143.68,186.52 146.36,184.54 149.04,182.56 151.72,180.58 154.40,178.60 157.08,176.62 159.76,174.64 162.44,172.66 165.12,170.68 167.80,168.70 170.48,166.72 173.16,164.74 175.84,162.76 178.52,160.78 181.20,158.80 183.88,156.82 186.56,154.84 189.24,152.86 191.92,150.88 194.60,148.90 197.28,146.92 199.96,144.94 202.64,142.96 205.32,140.98 208.00,139.00 210.68,137.02 213.36,135.04 216.04,133.06 218.72,131.08 221.40,129.10 224.08,127.12 226.76,125.14 229.44,123.16 232.12,121.18 234.80,119.20 237.48,117.22 240.16,115.24 242.84,113.26 245.52,111.28 248.20,109.30 250.88,107.32 253.56,105.34 256.24,103.36 258.92,101.38 261.60,99.40 264.28,97.42 266.96,95.44 269.64,93.46 272.32,91.48 275.00,89.50 277.68,87.52 280.36,85.54 283.04,83.56 285.72,81.58 288.40,79.60 291.08,77.62 293.76,75.64 296.44,73.66 299.12,71.68 301.80,69.70 304.48,67.72 307.16,65.74 309.84,63.76 312.52,61.78 315.20,59.80 317.88,57.82 320.56,55.84 323.24,53.86 325.92,51.88 328.60,49.90 331.28,47.92 333.96,45.94 336.64,43.96 339.32,41.98 342.00,40.00\"/><polyline fill=\"none\" stroke=\"#6953a8\" stroke-width=\"2.8\" stroke-dasharray=\"7 4\" points=\"74.00,183.00 342.00,183.00\"/><polyline fill=\"none\" stroke=\"#a45b2b\" stroke-width=\"2.8\" points=\"74.00,73.00 342.00,73.00\"/><text transform=\"translate(208 303)\" text-anchor=\"middle\" font-size=\"14\" fill=\"currentColor\"><tspan x=\"0\" dy=\"0\">Fault duration (s)</tspan></text><text transform=\"translate(20 139) rotate(-90)\" text-anchor=\"middle\" font-size=\"14\" fill=\"currentColor\"><tspan x=\"0\" dy=\"0\">Accumulated I²t (A²·s)</tspan></text></svg><div class=\"visual-legend\"><span><i style=\"background:#2459a8\"></i>Constant-current integral</span><span><i style=\"background:#6953a8\"></i>Example downstream clearing = 1000 (dashed)</span><span><i style=\"background:#a45b2b\"></i>Example upstream pre-arcing = 3000</span></div></figure>"
      }
    }
  ]
}